Description
Schneider Electric 240v AC to 24v DC 0.6A single pole power supply.
Frequently bought with C-Bus Automation Controller's 5500AC2 and 5500NAC2.
Main
Range of product | Modicon Power Supply |
---|---|
Product or component type | Power supply |
Power supply type | Regulated switch mode |
Variant option | Modular |
Enclosure material | Plastic |
Nominal input voltage | 100...240 V AC single phase 100...240 V AC 2 phases |
Rated power in W | 15 W |
output voltage | 24 V DC |
Power supply output current | 0.625 A |
Complementary
Input voltage limits | 90...264 V AC |
---|---|
Nominal network frequency | 50…60 Hz |
Network system compatibility | TN TT IT |
maximum leakage current | 0.25 mA 240 V AC |
input protection type | Integrated fuse (not interchangeable) 3.15 A External protection (recommended) 20 A Curve B External protection (recommended) 20 A Curve C External protection (recommended) 2 A Curve B External protection (recommended) 2 A Curve C |
inrush current | 15 A at 115 V 30 A at 230 V |
power factor | 0.51 at 115 V AC 0.40 at 230 V AC |
efficiency | 81 % at 115 V AC 81 % at 230 V AC |
Power dissipation in W | 3.5 W |
current consumption | < 0.4 A 115 V AC < 0.25 A 230 V AC |
Turn-on time | < 2 s |
holding time | > 10 ms 115 V AC > 60 ms 230 V AC |
Startup with capacitive loads | 3000 µF |
Residual ripple | < 100 mV |
Expected capacitor life time | 10 year(s) |
meantime between failure [MTBF] | 3000000 h at 25 °C, full load 1000000 h at 55 °C, 80 % load |
output protection type | Against overload and short-circuits, protection technology: automatic reset Against over temperature, protection technology: manual reset Against overvoltage, protection technology: manual reset |
connections - terminals | Screw connection: 0.5...1.5 mm², (AWG 20...AWG 16) without wire end ferrule for input/output Screw connection: 0.5...1 mm², (AWG 20...AWG 18) with wire end ferrule for input/output |
line and load regulation | < 0.5 % network in line < 1 % network 0 to 100 % load |
status LED | 1 LED (green) output voltage |
Depth | 55.6 mm |
Height | 91 mm |
Width | 18 mm |
Net weight | 0.101 kg |
Output coupling | Serial |
mounting support | Top hat type TH35-15 rail conforming to IEC 60715 Top hat type TH35-7.5 rail conforming to IEC 60715 Double-profile DIN rail panel mounting |
supply | SELV conforming to EN/IEC 60950-1 SELV conforming to EN/IEC 60204-1 SELV conforming to IEC 60364-4-41 |
dielectric strength | 3000 V AC input/output |
Environment
Standards | EN 62368-1 EN/IEC 61010-1 EN 61010-2-201 EN/IEC 61204-3 EN 61000-6-1 EN 61000-6-2 EN 61000-6-3 EN 61000-6-4 EN 61000-3-2 EN 61000-3-3 UL 62368-1 UL 61010-1 UL 61010-2-201 CSA C22.2 No 62368-1 CSA C22.2 No 61010-1 CSA C22.2 No 61010-2-201 EN/IEC 62368-1 |
---|---|
product certifications | CE CUL listed CUL recognized RCM CB Scheme EAC KC NEC: class 2 |
operating altitude | < 2000 m overvoltage category III 2000 m...5000 m overvoltage category II |
shock resistance | 100 m/s² for 11 ms |
IP degree of protection | IP20 |
Ambient air temperature for operation | -25…55 °C without current derating mounting position A < 2000 m 55…70 °C with current derating of 2.67 % per °C mounting position A < 2000 m |
electrical shock protection class | Class II without PE connection |
Pollution degree | 2 |
vibration resistance | 3 mm (f= 2…9 Hz) conforming to IEC 60721-3-3 10 m/s² (f= 9…200 Hz) conforming to IEC 60721-3-3 |
Electromagnetic immunity | Immunity to electrostatic discharge - test level: 6 kV (contact discharge) conforming to EN/IEC 61000-4-2 Immunity to electrostatic discharge - test level: 9 kV (air discharge) conforming to EN/IEC 61000-4-2 Electromagnetic field immunity test - test level: 10 V/m (80 MHz...2 GHz) conforming to EN/IEC 61000-4-3 Electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to EN/IEC 61000-4-3 Electromagnetic field immunity test - test level: 3 V/m (2.7...6 GHz) conforming to EN/IEC 61000-4-3 Immunity to fast transients - test level: 4 kV (on input-output) conforming to EN/IEC 61000-4-4 Surge immunity test - test level: 3 kV (between power supply and earth) conforming to EN/IEC 61000-4-5 Surge immunity test - test level: 1.5 kV (between phases) conforming to EN/IEC 61000-4-5 Immunity to conducted disturbances - test level: 10 Vrms (0.15...80 MHz) conforming to EN/IEC 61000-4-6 Immunity to magnetic fields - test level: 30 A/m (50...60 Hz) conforming to EN/IEC 61000-4-8 Immunity to voltage dips - test level: 100 % (1 cycle) conforming to EN/IEC 61000-4-11 Immunity to voltage dips - test level: 60 % (10 cycles) conforming to EN/IEC 61000-4-11 Immunity to voltage dips - test level: 30 % (25 cycles) conforming to EN/IEC 61000-4-11 Disturbing field emission conforming to EN 55016-2-3 Limits for harmonic current emissions conforming to EN 61000-3-2 Conducted disturbance emission conforming to EN 55016-1-2 Conducted disturbance emission conforming to EN 55016-2-1 |
electromagnetic emission | Conducted emissions conforming to EN 61000-6-3 Radiated emissions conforming to EN 61000-6-4 |
DOWNLOADS
Payment & Security
Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.